Sold out
Roll over or click image to zoom in

[Hletech] R134a industrial/commercial high-temperature heat pump unit, 85 ℃ high temperature, food drying, industrial cleaning, process hot water, alternative boiler energy-saving solution

Hletech
Out of stock
$0.00
customers are viewing this product

System optimization design can achieve high-temperature water output, meeting the process water requirements that ordinary hot water heat pumps cannot adapt to for commercial washing, food processing, bathing, and other purposes. The COP performance is excellent, with energy consumption far lower than that of electric heating equipment and fuel boilers, significantly reducing daily operating energy consumption expenses and carbon emissions, in line with European energy conservation and emission reduction policies. Variable frequency models can dynamically adjust the output load based on real-time water consumption, reducing frequent start stop of the unit and improving energy efficiency under variable load conditions, making them suitable for fluctuating water usage scenarios. Strengthen the heat exchange system to stably produce hot water under various outdoor temperature conditions; Optional low-temperature enhanced models to meet the continuous water supply needs during the cold season in Northern Europe. Support parallel operation of multiple units to increase total hot water production capacity; Flexible scheme design, supporting staged installation and later expansion; A single failure does not affect the continuous operation of the entire system. Accurate temperature control logic, supporting timed operation and load management; Built in WiFi module, remote parameter adjustment, real-time monitoring of operating status, fault alarm, and operation data recording, facilitating centralized operation and maintenance management. Equipped with multiple protections such as high and low voltage protection, overheating protection, dry burning prevention, water flow monitoring, anti freezing, and fault self checking, automatic alarm for abnormalities ensures continuous and safe operation around the clock. Optimized layout of fans and compressors with shock-absorbing structures, resulting in minimal vibration and low operating noise, suitable for placement in factory areas and surrounding machine rooms.

Model KFXRS- 39IIH/R3 78IIH/R3 152IIH/R3
Nominal Condition Rated Power Input W 8500 17100 34000
Nominal Heating Capacity W 39000 78000 155000
COP W/W 4.59 4.56 4.56
Current A 14.95 30.07 59.79
Rated Voltage / Frequency 380V3N~50Hz 380V3N~50Hz 380V3N~50Hz
Max Input Power / Current W/A 12000/22 24000/44 48000/88
Rated Circulating Water Flow m³/h 3.78 13.41 26.66
Water Side Pressure Drop kPa 41 42 50
Operating Range -10~46 -10~46 -10~46
Max Outlet Water Temp. C 80 80 80
Nominal Hot Water Output L/h 838 1677 3332
Dimensions (L×W×H) mm 1250×1000×1400 2000×1100×2130 2400×1200×2300
Refrigerant Name R134a R134a R134a
Electric Shock Protection Type l l l
Waterproof Class IPX4 IPX4 IPX4
Noise Level dB(A) 60 64 68
Circulating Water Pipe Pipe Diameter mm DN25 DN40 DN80
Connection Type Threaded Connection Flange Flange
Unit Weight kg 340 910 1410
[Hletech] R134a industrial/commercial high-temperature heat pump unit, 85 ℃ high temperature, food drying, industrial cleaning, process hot water, alternative boiler energy-saving solution
You have successfully subscribed!